Cassette fancoil, 4-tube system, 570x570x295 mm, total nominal refrigerating capacity 3.08 kW (air entry temperature: 19°C; water entry temperature: 7°C, temperature difference: 5°C), total nominal heating capacity 1.94 kW (air entry temperature: 20°C; water entry temperature: 70°C), 3 speeds, nominal water flow 0.626 m³/h, nominal air flow 430 m³/h and nominal sound power 41 dBA, with 3-way valve with bypass (4-way), with actuator, for the cold battery, and 3-way valve with bypass (4-way), with actuator, for the heat battery. Including elements for ceiling suspension. Totally mounted, connected and put into operation by the installing company for the verification of its correct functioning.